Last modified by writer on 2022/08/18 15:25

Show last authors
1 You will need a frequency converter (hereinafter referred to as the FC) with support for Modbus RTU control, such as Toshiba VF-S11, to control the spindle via Modbus via the PLCM-B1-G2 expansion board.
2
3 Modbus spindle control setting procedure:
4
5 1. Set FC to the control mode using the Modbus RTU protocol (RS-485) and remember the COM port settings in FC (count of bits per second, data bits, parity and stop bits).
6
7 Example for Toshiba VF-S11.
8
9 |=(% style="text-align: center; width: 150px;" %)Function code|=(% style="text-align: center; width: 100px;" %)Value|=(% style="text-align:center" %)Description
10 |(% style="width:150px" %)F800|(% style="width:100px" %)3|Transfer rate: 9600 bits per sec
11 |(% style="width:150px" %)F801|(% style="width:100px" %)1|Parity check enabled
12 |(% style="width:150px" %)F802|(% style="width:100px" %)1|Device number on the bus
13 |(% style="width:150px" %)F829|(% style="width:100px" %)1|Communication Protocol: Modbus RTU
14
15 (% style="margin-left: 30.0px;" %)
16 2. Connect FC to the PLCM-B1-G2 expansion board via RS-485 interface.
17
18 (% style="margin-left: 30.0px;" %)
19 3. Purchase the "[[MODBUS protocol support>>url:http://pumotix.ru/#soft||shape="rect"]]" option or activate a trial period for this option in the menu "Configuration" → "License Manager" → "Common".
20
21 (% style="margin-left: 30.0px;" %)
22 4. Enable and configure Modbus in the menu "Configuration" → "Modbus Setup".
23
24 Create new Modbus-master. Number of COM port is PLCM. The rest of the settings should be exactly the same as in the FC (in the screenshot, an example of a standard configuration of the COM port of Toshiba VF-S11).
25
26 [[image:modbus_master_en.png||alt="master_plcm.png" data-xwiki-image-style-alignment="center" height="300" width="367"]]
27
28 You need to add registers to control the FC and read statuses from FC. For example you need to configure registers named **SpindleMode**, **SpindleRPM** and **SpindleStatus**.
29
30 We recommend using exactly these names, since in the future, registers will be accessed from background operations by their names.
31
32 (% class="non-break" %)
33 |=(% style="text-align: center;" %)Name|=(% style="text-align: center;" %)Master|=(% style="text-align: center;" %)Address|=(% style="text-align: center;" %)Register|=(% style="text-align: center;" %)Register type
34 |SpindleMode|PLCM|1|64000|Output
35 |SpindleRPM|PLCM|1|64001|Output
36 |SpindleStatus|PLCM|1|64769|Input
37
38 {{success}}
39 Register numbers must be specified as decimal values.
40 {{/success}}
41
42 {{warning}}
43 These values ​​can be indicated in HEX (hexadecimal) in the instructions for the frequency converter. For example, 0x1001, 0x1002.
44 {{/warning}}
45
46 (% style="margin-left: 30.0px;" %)
47 5. Create new background operation (macro) through [[the macro manager>>doc:Руководство пользователя.Описание M-кодов.Управление макросами и фоновыми операциями.WebHome]].
48
49 The main task of the background macro is to monitor the current state and spindle speed and send the values to the frequency converter via Modbus.
50
51 An example of background operation **modbus_spindle.bm** for ModBus spindle control via FC Toshiba VF-S11 posted in attachment. This file must be added to background operations list.
52
53 **[[Download background operation>>attach:modbus_spindle.zip]]**
54
55 {{warning}}
56 Access to Modbus registers from macros is done by the name of the Modbus register case sensitive! For example **SpindleRPM** and **SpindleRpm** are different registers.
57 {{/warning}}
58
59 (% style="margin-left: 30.0px;" %)
60 6. Enable the background operation. Make sure that the operation has started and is working properly. This will be indicated by the green indicator to the right of the operation name.
61
62 [[image:Macros_Manager_wndw.png||alt="2021-11-29 14_18_03-Управление макросами.png" data-xwiki-image-style-alignment="center" height="500" width="681"]]